Welcome: B.B.Battery (Taiwan) Co., Ltd.
Language: Chinese ∷  English

BP100-12-BB Battery12V100AH-The universal series is suitable for UPS uninterruptible power supply, electric tools, and emergency lights

Specifications:
- **Nominal Voltage:** 12 V
- **Nominal Capacity:** 100Ah @ 20-hour rate F.V. (1.75V/cell)
- **Approx. Weight:** 32.7Kg (72.1lbs.)
- **Terminals:** B3 (Fitting M6 bolt & nut), optional I2
- **Internal Resistance:** ≤4.5mΩ (Fully Charged)
- **Max. Discharge Current:** 800 A (5 sec.)
- **Max. Charge Current:** 30 A
- **Operating Temperature Range:**
- Charge: 0°C to 40°C (32°F to 104°F)
- Discharge: -20°C to 50°C (-4°F to 122°F)
- Storage: -20°C to 40°C (-4°F to 104°F)
- **Container Material:**
- Standard: ABS (UL94 HB) BP100-12
- Optional: Flame Retardant ABS (UL94 V-0) BP100-12FR

BP100-12-BB Battery12V100AH

### VRLA Rechargeable Battery
#### BP100-12

---

### Features:
- **Maintenance Free:** No water topping-up required.
- **Non-spillable:** No free electrolyte.
- **Low Self Discharge:** Less than 3% per month.
- **Vertical & Horizontal Installations:** Can be used in both orientations.
- **Integrated Flame Arrestor:** Ensures safety.
- **Carry Handles:** For easy installation.

### Applications:
- UPS
- Telecom Systems
- Switch Boards
- Elevated Platforms
- Photovoltaic Systems
- Emergency Lighting
- Golf Carts

### Specifications:
- **Nominal Voltage:** 12 V
- **Nominal Capacity:** 100Ah @ 20-hour rate F.V. (1.75V/cell)
- **Approx. Weight:** 32.7Kg (72.1lbs.)
- **Terminals:** B3 (Fitting M6 bolt & nut), optional I2
- **Internal Resistance:** ≤4.5mΩ (Fully Charged)
- **Max. Discharge Current:** 800 A (5 sec.)
- **Max. Charge Current:** 30 A
- **Operating Temperature Range:**
  - Charge: 0°C to 40°C (32°F to 104°F)
  - Discharge: -20°C to 50°C (-4°F to 122°F)
  - Storage: -20°C to 40°C (-4°F to 104°F)
- **Container Material:**
  - Standard: ABS (UL94 HB) BP100-12
  - Optional: Flame Retardant ABS (UL94 V-0) BP100-12FR

### Complies with Standards:
- IEC 60896-21/22
- JIS C 8704-2
- GB/T 19638.2

### Dimensions (mm/inch):
- **Length:** 329±2.0 (12.95±0.08)
- **Width:** 172±2.0 (6.77±0.08)
- **Container Height:** 215±2.0 (8.46±0.08)
- **Total Height:**
  - B3: 238±2.0 (9.37±0.08)
  - I2: 218.5±2.0 (8.60±0.08)
- **Terminal Hardware Initial Torque:** B3, I2: 5.5Nm±5%

### Constant Power Discharge Characteristics at 25°C/77°F (Unit: W):
| Discharge Time | 30 Min | 1 Hr | 3 Hr | 5 Hr | 10 Hr | 20 Hr |
|----------------|--------|------|------|------|-------|-------|
| **1 Hr**       | 1256   | 727  | 291.5| 201.0| 112.3 | 159.1 |
| **15 Min**     | 1304   | 749.6| 297.3| 204.0| 114.0 | 60.0  |
| **30 Min**     | 1334   | 763.1| 300.0| 205.1| 114.5 | 60.3  |
| **1.5 Hr**     | 1353   | 772.3| 302.0| 205.8| 114.9 | 60.5  |
| **2 Hr**       | 1366   | 780.0| 303.9| 206.4| 114.9 | 60.5  |

### Constant Current Discharge Characteristics at 25°C/77°F (Unit: A):
| Discharge Time | 5 Hr  | 10 Hr | 20 Hr |
|----------------|-------|-------|-------|
| **5 Hr**       | 16.75 | 4.93  | 4.36  |
| **10 Hr**      | 17.00 | 9.50  | 5.00  |
| **20 Hr**      | 17.09 | 9.55  | 5.03  |
| **5 Hr**       | 17.15 | 9.58  | 5.04  |
| **10 Hr**      | 17.20 |       |       |

### End Voltage (F.V) of Discharge:
| Discharge Time | 15 Min | 30 Min | 1 Hr   | 1.5 Hr | 2 Hr   |
|----------------|--------|--------|--------|--------|--------|
| **10.8V**      | 2065   | 2160   | 2226   | 2278   | 2323   |
| **10.5V**      |        |        |        |        |        |
| **10.2V**      |        |        | 203.6  | 115.8  | 9.9V   |
| **9.9V**       |        |        | 65.55  | 25.33  | 9.58   |
| **9.6V**       |        |        |        |        | 116.9  |

INQUIRY

Scan the qr codeClose
the qr code