Welcome: B.B.Battery (Taiwan) Co., Ltd.
Language: Chinese ∷  English

FTB110-12-BB Battery12V110AH-Front terminal narrow lead-acid batteries are suitable for UPS systems, emergency lighting, and security systems

VRLA Rechargeable Battery
FTB110-12

FEATURES
- Absorbent Glass Mat technology for efficient gas recombination
- Thermally welded case-to-cover bond to ensure a leak-proof case
- Front accessible terminal for ease of assembly
- Carry handles for ease of installation
- Strengthened rib design to maintain structural integrity
- Flame-arrestor is installed to ensure safety
- Battery design allows for 48VDC configuration in a standard 23" rack
- One-way self-resealing safety valve for long life guarantee

APPLICATIONS
Telecom
UPS
Broadband
Electric Utility
Railroad Signal
Central Office

SPECIFICATIONS
- Nominal Voltage: 12V
- Nominal Capacity: 110Ah @ 8-hour rate F.V. (1.75V/cell)
- Approx. Weight: 41.1Kg (90.6lbs.)
- Terminals: L1 (M8 Male Stud)
- Internal Resistance: ≤3.0mΩ (Fully Charged)
- Max. Discharge Current: 800A (5 sec.)
- Max. Charge Current: 27.5A
- Operating Temperature Range:
- Charge: 0°C-40°C (32°F~104°F)
- Discharge: -20°C-50°C (-4°F~122°F)
- Storage: -20°C-40°C (-4°F~104°F)
- Safety Valve Opening pressure: 10-35 kPa
- Container Material:
- Standard: ABS (UL94 HB) FTB110-12
- Optional: Flame Retardant ABS (UL94 V-0) FTB110-12FR

DIMENSIONS (mm/inch)
- Length: 560.0+2.0 (22.05+0.08)
- Width: 125.0+2.0 (4.92+0.08)
- Container Height: 230.0+2.0 (9.06+0.08)
- Total Height: 230.0+2.0 (9.06+0.08)

FTB110-12-BB Battery12V110AH

VRLA Rechargeable Battery
FTB110-12

FEATURES
- Absorbent Glass Mat technology for efficient gas recombination
- Thermally welded case-to-cover bond to ensure a leak-proof case
- Front accessible terminal for ease of assembly
- Carry handles for ease of installation
- Strengthened rib design to maintain structural integrity
- Flame-arrestor is installed to ensure safety
- Battery design allows for 48VDC configuration in a standard 23" rack
- One-way self-resealing safety valve for long life guarantee

APPLICATIONS
Telecom
UPS
Broadband
Electric Utility
Railroad Signal
Central Office

SPECIFICATIONS
- Nominal Voltage: 12V
- Nominal Capacity: 110Ah @ 8-hour rate F.V. (1.75V/cell)
- Approx. Weight: 41.1Kg (90.6lbs.)
- Terminals: L1 (M8 Male Stud)
- Internal Resistance: ≤3.0mΩ (Fully Charged)
- Max. Discharge Current: 800A (5 sec.)
- Max. Charge Current: 27.5A
- Operating Temperature Range:
  - Charge: 0°C-40°C (32°F~104°F)
  - Discharge: -20°C-50°C (-4°F~122°F)
  - Storage: -20°C-40°C (-4°F~104°F)
- Safety Valve Opening pressure: 10-35 kPa
- Container Material:
  - Standard: ABS (UL94 HB) FTB110-12
  - Optional: Flame Retardant ABS (UL94 V-0) FTB110-12FR

DIMENSIONS (mm/inch)
- Length: 560.0+2.0 (22.05+0.08)
- Width: 125.0+2.0 (4.92+0.08)
- Container Height: 230.0+2.0 (9.06+0.08)
- Total Height: 230.0+2.0 (9.06+0.08)

TERMINAL TYPE
- Terminal: L1 (M8 Male Stud)
- Terminal Hardware Initial Torque: 10.0Nm ±5%

Constant Power Discharge Characteristics at 25°C/77°F
(Unit: W/cell)
| Discharge Time | 90% | 1.85V | 1.75V | 1.80V | 1.60V |
|----------------|------|-------|-------|-------|-------|
| 15 Min         | 146.7| 195.7 | 214.2 | 233.0 | 244.4 |
| 30 Min         | 122.6| 134.8 | 143.3 | 148.6 | 159.5 |
| 45 Min         | 103.3| 106.8 | 108.1 | 110.4 | 113.5 |

Constant Current Discharge Characteristics at 25°C/77°F
(Unit: W)
| Discharge Time | 1.90V | 1.85V | 1.80V | 1.75V | 1.70V | 1.65V | 1.60V |
|----------------|-------|-------|-------|-------|-------|-------|-------|
| 15 Min         | 123.9 | 146.5 | 167.9 | 187.7 | 203.0 | 212.3 | 216.2 |
| 30 Min         | 102.1 | 113.5 | 121.4 | 125.9 | 128.8 | 130.6 | 131.9 |
| 45 Min         | 74.6  | 82.1  | 87.1  | 90.0  | 91.8  | 93.0  | 93.9  |